Line break valve (pipe burst protection)

Description

Line break valves detect a rupture in a pipe to be monitored and switch as soon as the pressure drop rate [bar/min] exceeds a preset value. In the event of ‘normal’ pressure changes in the pipework, the line break valve does not react.

If it has tripped, it must be manually re-engaged (‘armed’) on site. In contrast to electronic LBS, this device works completely hydraulically and mechanically and can therefore be used independently to protect a pipeline in remote areas.

Symbol

Linebreak Ventil

Technical data

Size:DN3 / DN6 / DN10
Pressure range:PN100 (PN200)
Material:Steel, aluminium
Function:2/2, 3/2 (NO / NC)
Media:Natural gas, nitrogen, oxygen
Options:Limit switch, adjustable pressure drop rate 0.5-7 bar/min
Flow rate:Up to 15 l/min

View / dimension sheet